Laars FT (wall , floor ) Natural Gas AND LP Combustion Analysis Result #'s .
Laars MFTCW, MFTHW, FTCF AND FTHF ALL SIZES
Combustion Analysis Result #'s streamlined for best results:
All Adjustments are to be performed and tested in LOW FIRE ONLY
NATURAL GAS LOW FIRE
CO2 Carbon Dioxide= 8.5%-8.8%
O2 Oxygen=5.5%-5.8%
Excess Air=35%-38%
LP (Propane) LOW FIRE
CO2 Carbon Dioxide=9.0%-9.5%
O2 Oxygen=7.0%-7.5%
Excess Air=50%-55%
* These are approximate "Best Condition" results depending on differing factors of boiler placement, exhaust and intake piping , gas pressures, gas pipe sizing, combustion analyzer accuracy , analyzer calibration , etc.
See attachments for examples of combustion analysis printouts for both fuels (natural and LP ) !