LAARS LT/Bradford White Infiniti GS Series- Error 42 -Wall Hung Water Heaters -Vent Piping Installation- Intake and Exhaust.

LAARS LT/Bradford White Infiniti GS Series- Error 42 -Wall Hung Water Heaters -Vent Piping Installation- Intake and Exhaust.

LAARS LT/Bradford White Infinity GS Series Wall Hung Water Heaters.

Error 42:Exhaust (Hard Lockout).

APS (Air Pressure Switch) - Closed is Normal, Open is Fault.
1. Press the Power button on the display controller to clear the Error Code.
2. Check APS and main controller connections. Ensure all are secure.
3. Check APS resistance. If resistance is zero, replace the air pressure switch (APS).
4. Check APS hose. Ensure it is connected and in good condition.
4. Check exhaust vent for blockages. 
Notes
NOTE:
â–  Vent pipe pitch and supports.
Vent pipe must pitch upward, toward the vent terminal, not less than 1/4" per foot, so that condensate will run back to the water heater to drain. Route vent (exhaust) pipe to the heater as directly as possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation Instruction. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe.