LAARS MFTCW, MFTHW, FTCF, FTHF Won't achieve HIGH Temperature. Boiler won't go into high fire.
An Outdoor
Temperature Reset Supplied with the Boiler MUST MUST MUST be used.
The D.O.E
(department of energy) regulations regarding outdoor temp. reset DOES affect
this boiler in most all serial # date of manufacturer #'s !
It has been noted
that all MFTHW . FTHF , FTCF and many MFTCW models are
affected .
As per the D.O.E ,
the maximum temperature achieved is 140 degrees F (minus the differential of 8 degrees F) without an outdoor sensor or
some form of external modulation. ie tekmar (0-10) , (4-20).
* For troubleshooting and testing purposes, a 100K resistor wired to the O/S terminals of the boiler (in place of outdoor sensor) can be utilized.