LAARS MFTHW DHW Priority with an Indirect Tank and Zone Panel
ATTACHED is a SAMPLE wiring
diagram for wiring a DHW
Indirect (notice the additional "RIB" relay as an add on, NOT
supplied)with MFTHW boiler(s).
This addresses the
ability of using a DHW sensor in the indirect tank while maintaining
DHW PRIORITY with zone
panels! Remember to select DHW SENSOR in
parameter 39:SA ! The default is AquA(aquastat) , so you will have to select
Sens (sensor).
The wiring diagram
shows cascaded MFTHW's BUT this can also be followed for a
Single boiler
application as well .
If any questions
speak with Kenny or Don.