Handy Steam Conversion Charts
🔧 Handy Steam Conversion Charts
🔥 Boiler Horsepower (BHP) Conversions
Unit
|
Equivalent
|
1 Boiler HP
|
= 33,475 BTU/hr
|
1 Boiler HP
|
= 34.5 lbs of
steam/hr
|
1 Boiler HP
|
≈ 0.069 GPM condensate
|
1 Boiler HP
|
= 1 gallon
(for feed tank sizing)
|
💧 Steam to Water Conversions
Unit
|
Equivalent
|
1 lb of steam
|
≈ 1,000 BTU released
(latent heat)
|
1 gallon of water
|
= 8.34 lbs
|
1 GPM
|
= 500 lbs/hr of
condensate
|
🌡️ Saturated Steam Pressure & Temperature
Pressure (PSIG)
|
Temp (°F)
|
0 (Atmospheric)
|
212°F
|
2
|
219°F
|
5
|
227°F
|
10
|
240°F
|
15
|
250°F
|
30
|
274°F
|
60
|
307°F
|
⚙️ Pressure to Head Conversion
PSI
|
Feet of Head
|
1 PSI
|
= 2.31 ft
|
5 PSI
|
= 11.55 ft
|
10 PSI
|
= 23.1 ft
|
📏 Condensate Pipe Sizing (Low Pressure Return)
Condensate Flow
(lbs/hr)
|
Suggested Pipe
Size
|
Up to 1,500
|
¾"
|
1,500–3,000
|
1"
|
3,000–6,000
|
1¼"
|
6,000–10,000
|
1½"
|
10,000–15,000
|
2"
|
Related Articles
Steam Conversion Charts
? Handy Steam Conversion Charts ? Boiler Horsepower (BHP) Conversions Unit Equivalent 1 Boiler HP = 33,475 BTU/hr 1 Boiler HP = 34.5 lbs of steam/hr 1 Boiler HP ≈ 0.069 GPM condensate 1 Boiler HP = 1 gallon (for feed tank sizing) ? Steam to Water ...
Steam Essentials: Choosing the Right Condensate Solution
Effectively managing condensate—the water formed when steam cools and condenses—is essential for keeping a steam system running efficiently and reliably. Two common solutions are condensate return tanks and boiler feed systems. This article explains ...
Sizing Condensate Return and Boiler Feeds
Condensate and Boiler Feed Pump Sizing 1. Determine heating load: BTU/hr. or Boiler H.P. or Lbs./hr. : ____________ 2. Convert heating load from Step 1 to GPM (actual) If BTU/hr is known: _________ Btu/hr ÷ 33,475 = ___________ BHP If BHP is known: ...
Laars LT Series Water Heater Propane Conversion Kits
LT Series tankless gas water heaters are now field gas convertible (natural gas / propane). Please note that this feature is applicable to models with serial numbers beginning with “F24” and later. The conversion kits are shown in the table below. ...
LAARS LT Recirculation Model LT199NRX1/LT199PRX1-Recirc programming functions and defaults.
The LAARS LT199NRX1/LT199PRX1 (recirc models) are program defaulted from the factory for NON recirc. To activate recirc function the water heater must be programmed to provide recirc function depending on the recirc option selected and piped in that ...