Unit |
Equivalent |
1 Boiler HP |
= 33,475 BTU/hr |
1 Boiler HP |
= 34.5 lbs of steam/hr |
1 Boiler HP |
≈ 0.069 GPM condensate |
1 Boiler HP |
= 1 gallon (for feed tank sizing) |
Unit |
Equivalent |
1 lb of steam |
≈ 1,000 BTU released (latent heat) |
1 gallon of water |
= 8.34 lbs |
1 GPM |
= 500 lbs/hr of condensate |
Pressure (PSIG) |
Temp (°F) |
0 (Atmospheric) |
212°F |
2 |
219°F |
5 |
227°F |
10 |
240°F |
15 |
250°F |
30 |
274°F |
60 |
307°F |
PSI |
Feet of Head |
1 PSI |
= 2.31 ft |
5 PSI |
= 11.55 ft |
10 PSI |
= 23.1 ft |
Condensate Flow (lbs/hr) |
Suggested Pipe Size |
Up to 1,500 |
¾" |
1,500–3,000 |
1" |
3,000–6,000 |
1¼" |
6,000–10,000 |
1½" |
10,000–15,000 |
2" |