Unit |
Equivalent |
|
1 Boiler HP |
= 33,475 BTU/hr |
|
1 Boiler HP |
= 34.5 lbs of steam/hr |
|
1 Boiler HP |
≈ 0.069 GPM condensate |
|
1 Boiler HP |
= 1 gallon (for feed tank sizing) |
|
Unit |
Equivalent |
|
1 lb of steam |
≈ 1,000 BTU released (latent heat) |
|
1 gallon of water |
= 8.34 lbs |
|
1 GPM |
= 500 lbs/hr of condensate |
|
Pressure (PSIG) |
Temp (°F) |
|
0 (Atmospheric) |
212°F |
|
2 |
219°F |
|
5 |
227°F |
|
10 |
240°F |
|
15 |
250°F |
|
30 |
274°F |
|
60 |
307°F |
|
PSI |
Feet of Head |
|
1 PSI |
= 2.31 ft |
|
5 PSI |
= 11.55 ft |
|
10 PSI |
= 23.1 ft |
|
Condensate Flow (lbs/hr) |
Suggested Pipe Size |
|
Up to 1,500 |
¾" |
|
1,500–3,000 |
1" |
|
3,000–6,000 |
1¼" |
|
6,000–10,000 |
1½" |
|
10,000–15,000 |
2" |