LWCO and High Limit Reset Types in Laars Mascot Units

LWCO and High Limit Reset Types in Laars Mascot Units

LWCO and High Limit Reset Types in Laars Mascot Units

Applies To: Mascot Heat Only, Mascot Combi, and LT/Instantaneous Water Heater Series

Last Updated: July 30, 2025

 

Summary

Mascot Heat Only and Mascot Combi units (all sizes) include:

Auto-reset Low Water Cutoff (LWCO)

Auto-reset High Limit

LT/Instantaneous Water Heater series include:

Manual-reset High Limit (reset via control panel)

No built-in LWCO

NYC Code Requirement: Built-in auto-reset functions do not satisfy local manual-reset mandates. Contractors must install external manual-reset LWCO and high-limit devices on system piping.

Detailed Overview

Unit Series

Built-In LWCO

Built-In High Limit

Reset Type

NYC Installation Requirement

Mascot Heat Only & Mascot Combi

Yes

Yes

Auto-reset

External manual-reset LWCO & high limit

LT / Instantaneous Water Heaters

No

Yes

Manual-reset (control panel)

No external reset required

Installation Notes for NYC

Per NYC code, the built-in auto-reset LWCO and high-limit controls in Mascot boilers do not meet manual-reset requirements. The installing contractor must provide and install:

A manual-reset LWCO (external)

A manual-reset high-limit device (external)

These must be mounted on the system piping outside the equipment enclosure.