Ten (10) Hydronic Rules of Thumb

Ten (10) Hydronic Rules of Thumb

Ten (10) Hydronic "Rules of Thumb"


  1.  PSI x 2.31 = feet of head (TDH, Total Dynamic Head) 
  2. GPM x Delta T x 500 = BTU/hour
  3. Pressure Drop for piping system = Linear Feet of Longest Circuit x .06
  4. Proper flow for boiler in GPM = Output BTU/hr divided by 10,000
  5. Static Height in feet / 2.31 + 4 PSI = Proper fill pressure
  6. Maximum Capacity:
    1. 1/2" Pipe = 1.3 GPM = 13,000 BTU/hr
    2. 3/4" Pipe = 3.5 GPM = 35,000 BTU/hr
    3. 1" Pipe = 7.5 GPM = 75,000 BTU/hr
    4. 1 1/4" Pipe = 12 GPM = 120,000 BTU/hr
    5. 1 1/2" Pipe = 20 GPM = 200,000 BTU/hr
    6. 2" Pipe = 45 GPM = 450,000 BTU/hr
  7. Maximum output radiant floor = 35 BTU / square foot
  8. Typical output snowmelt system = 125 BTU / square foot
  9. "ESTIMATE" for heat loss of "new building" = 35 BTU / square foot
  10. "ESTIMATE" for heat loss of "old building" = 50 BTU / square foot


    • Related Articles

    • Proper Armstrong Pump Installation in Grooved Pipe Systems

      Groove fittings have become a widely used manner of connecting piping systems.  It has been noticed however, that when installed improperly, there can be some undesired flex that occurs in the piping at the fitting locations.  When mounting an ...
    • Look Like a Master by Knowing These 3 Venting Rules - Category 1 (Natural Draft)

      A boiler locks out. A tech blames the gas valve. The owner thinks they bought a lemon. The usual fix? Swap parts, blame the equipment, move on. But what if the problem isn’t the boiler? Most people never check the venting—at least not until there’s ...
    • Handy Steam Conversion Charts

      ? Handy Steam Conversion Charts ? Boiler Horsepower (BHP) Conversions Unit Equivalent 1 Boiler HP = 33,475 BTU/hr 1 Boiler HP = 34.5 lbs of steam/hr 1 Boiler HP ≈ 0.069 GPM condensate 1 Boiler HP = 1 gallon (for feed tank sizing) ? Steam to Water ...
    • LAARS FT 301/399 I/O Manual

      LARRS FT 301/399 I/O Manual Introduction Piping Wiring Programming Error Codes Troubleshooting Parts CLICK ON ATTACHMENTS TO VIEW
    • Sizing Condensate Return and Boiler Feeds

      Condensate and Boiler Feed Pump Sizing 1. Determine heating load: BTU/hr. or Boiler H.P. or Lbs./hr. : ____________ 2. Convert heating load from Step 1 to GPM (actual) If BTU/hr is known: _________ Btu/hr ÷ 33,475 = ___________ BHP If BHP is known: ...