Tekmar 356 (injection mix control) Quick Set Up Guide.

Tekmar 356 (injection mix control) Quick Set Up Guide.

Tekmar 356 Injection mix control quick set up :

Room= 70 degrees
Outdoor design= 10 degrees
Terminal unit #1
Design indoor= 70 degrees
Design Supply= 130 degrees
Mix Temp= 145 degrees
Sensor Location = Supply
Minimum Boiler Temp= Off or Low (fine with condensing boilers, should be higher with cast iron boilers ) . 
WWSD= 70 degrees
Unit of Measure = F